Applications

  • For illuminating the interior of tanks, hoppers, silos, agitators
    and other - normally closed - vessels and reactors as well as
    visual flow indicators in potentially explosive environments.

    Gas: Zones 1 and 2,

    Dust: Zones 21 and 22.
  • Suitable for use in food processing industries
  • This Ex-type sight glass luminaire is designed for universal
    applications in potentially explosive environments. It is
    ideal for use in combined sight and light-glass arrangements,
    either as a single flange version or with two separate flanged
    ports.
Operating conditions
  • Independent of the internal pressure / vacuum in vessel.
    Under no circumstances should a sight glass luminaire be
    used on its own to close a vessel port or to replace the
    cover flange or the sight glass / luminaire assembly.
Operating temperature
  • Sight glass luminaires of this series are approved for use in ambient
    temperatures of up to 60°C, depending on the lamp bulb fitted.

Protection
  • IP 65 and IP 67 to DIN EN 60529

Certification

  • EC Type-Examination Certificate BVS 08 ATEX E 133
  • II 2G Ex d IIC T3/T4/T6/120°C Gb
  • II 2D Ex tb IIIC T80/T120/T130/T195°C Db

 

    Atex Cerfificate USL05-Ex

Materials

  • Body of luminaire: Corrosion-resistant die-cast aluminium alloy, GK-ALSi10Mg
  • Cable gland with pressure-tight resin-cast connecting cable, Sinotherm 110 H05GG-F 3G, 1.5 mm², standard cable length: 2 m
  • Protective conductor terminal: Internal terminal already connected, additional external protective conductor terminal on enclosure
  • Light exit: Bonded unit made of aluminium ring and glass; Viton seal
Advantages
  • Compact yet powerful:
    Dazzle-free illumination; for use with circular sight glass fittings to
    DIN 28120/DIN 28121 or similar, with screw-type sight glass fittings in compliance with DIN 11851, and in visual flow indicators
  • Optimal design of screw-type lens ensures max. light efficiency.
  • Convenient lamp replacement thanks to optimised screw-type opening

Operation Voltage

  • Without integrated transformer:
    12 V... Halogen lamp 5 W or 20 W

    24 V... Halogen lamp 20 W 230 V... LED illuminant 4 W
  • With integrated transformer; PTC-protected:
    120 V... Halogen lamp 12 V/5 W 230 V...
    Halogen lamp 12 V/5 W

Type USL05-Ex/
Type USL
05-LED-Ex


Nominal size

Built-in-
transformer

Halogen lamp
or LED-illuminat

Ambient temperature range
-20°C < Ta < +40°C -20°C < Ta < +60°C

 

 

 

Voltage

Socket

 

 

 

 

(12 V) 5 W

12

without

12 V / 5 W

G4

2G T6

2D T180°C

2G T4

2D T130°C

(120 V / 12 V) 5 W

120 ~

with

12 V / 5 W

G4

2G T6

2D T180°C

2G T4

2D T130°C

(230 V / 12 V) 5 W

230 ~

with

12 V / 5 W

G4

2G T6

2D T180°C

2G T4

2D T130°C

(12 V) 20 W

12

without

12 V / 20 W

G4

2G T4

2D T130°C

2G T3

2D T195°C

(24 V) 20 W

24

without

24 V / 20 W

G4

2G T4

2D T130°C

2G T3

2D T195°C

(230 V) 4 W-LED

230

without

230 V /
4 W-LED

GZ10

 

2G T6

2D T180°C